Specificatii tehnice
Tensiune intrare | 380/400/415 VAC |
Frecventa intrare | 50/60 Hz |
Temperaturi de operare UPS | 0°C ÷ 40°C |
Model | ZRTM 300K |
Putere | 450 / 500 |
Numar de faze intrare : iesire | 3:3 |
Intrare
Tensiune | 380 / 400 / 415 VAC |
Plaja tensiune | -43% ÷ 25% |
Frecventa | 50/60 Hz |
Gama frecventa | 20% ÷ +20% |
THDi | <3% |
Factor de putere intrare | ≥0,99 |
Iesire
Tensiune | 380 / 400 /415 VAC |
Factor de putere | 1,0 |
Reglare tensiune static / dinamic | ±1% / ±2% |
Frecventa | 50/60 Hz ±0,05 Hz |
Capacitate supraincarcare | 110% – 10 min, 125% – 1 min., 150% – 5 sec., >150% – 200 ms |
Supraincarcare Bypass | 125% – lucru constant, 130% – 10 min., 150% – 1 min., > 150% – 300 ms |
Capacitate scurtcircuit: | 340% din curentul nominal cu 200 ms |
Eficienta in modul On-line | >96% |
Randament Eco mode | 99% |
Factor de creasta | 5:1 |
Baterii
Tip | Fara mentenanta, sigilate VRLA |
Pornire la rece | Da |
Configurare baterii | 30 ÷ 40 buc, 12V |
Timp de incarcare | 3-8 ore cu pana la 90% capacitate |
Greutate si dimensiuni
Dimensiunile UPS (L x l x h) | 1300 x 1100 x 2000 mm |
Greutate UPS | 855 kg I 900 kg |
Comunicatii
Mod operare indicatori | Display LCD 7’’, indicatori LED x4, alarma sonora, LCD în fiecare modul de alimentare |
Comunicatii | RS232, RS485, MODBUS RTU/ASCII, USB, Dry Contact, SNMP , REPO, sloturi paralele |
Ambient
Nivel zgomot – dependent de sarcina si temperatura | < 62 dB (A) |
Temperatura de functionare pentru UPS | 0°C ÷ 40°C |
Temperatura de functionare recomandata pentru UPS | 15°C ÷ 25°C |
Temperatura stocare | -15°C ÷ 55°C |
Umiditate | 5 ÷ 95% (fără condensare) |
Standarde
Rezistenta la interferente | EN 62040-2:2005, EN 62040-2:2006, EN 60950-1, CE |
Optiuni
Card SNMP |
Panou status la distanta |
Bypass mentenanta extern neintreruptibil |
Card modbus si conacte libere de potential |
Software |
Cabinete de baterii sau rack-uri |